    Variable MODBUS_MAX_WRITE_REGISTERSConst

    MODBUS_MAX_WRITE_REGISTERS: 123

    Registers one FC16 (write multiple registers) transaction can carry.

    The limit follows from the PDU: 253 bytes, less the function code, the starting address, the quantity, and the byte count, leaves 246 bytes of payload.

    Many devices stop at a lower number than the specification allows. Pass PlanWritesOptions.maxRegistersPerWrite when the device says so.