    An Effect-TS service for Teco/Westinghouse A510 inverters that wraps @flux-control/effect-modbus-rs to manage the Modbus transport, map command and monitor registers, and apply typed schemas to all parameter groups (00–22).

    For the complete API reference, see the GitHub Pages documentation.

    TecoInverterService is a scoped Effect.Service that:

    • Manages the transport — Opens RTU or ASCII connections via @flux-control/effect-modbus-rs and caches a client per device ID.
    • Exposes operations — Typed command registers (start/stop, frequency, torque, analog/digital outputs) with read-modify-write semantics for bitfield registers.
    • Exposes monitoring — Typed monitor registers (state, errors, frequency, current, voltage, etc.) that decode wire values into domain types.
    • Maps parameters — Typed access to every A510 parameter (Groups 00–22) with proper scaling factors (×0.001, ×0.01, ×0.1, signed Int16, etc.) applied at encode/decode time.

    This project is under active development. Its API may change before the 1.0 release.

    bun add @flux-control/effect-teco-westinghouse-inverter
    

    Requires effect, @flux-control/effect-modbus-rs, and @flux-control/modbus-schema as peer dependencies.

    import { Console, Effect, Layer } from 'effect';
    import { TecoInverterService } from '@flux-control/effect-teco-westinghouse-inverter';
    import { SerialTransportService } from '@flux-control/effect-modbus-rs';

    const program = Effect.gen(function* () {
    const inverter = yield* TecoInverterService;
    const freq = yield* inverter.frequencyCommand(1).read();
    yield* inverter.frequencyCommand(1).update(50.0);
    });

    program.pipe(
    Effect.provide(
    Layer.provideMerge(
    TecoInverterService.Default(true),
    SerialTransportService.fromRtu({ portPath: '/dev/ttyUSB0', baudRate: 19200 }),
    ),
    ),
    Effect.scoped,
    Effect.runPromise,
    );

    TecoInverterService is a scoped Effect.Service that manages a Modbus client pool per device. Provide it with Effect.provide alongside a transport layer (SerialTransportService from @flux-control/effect-modbus-rs).

    Retry and reconnection are owned by the transport, not by this service. Configure them where the transport layer is built and they apply to every inverter operation — there is no per-call wiring to do here:

    SerialTransportService.fromRtu({
    portPath: '/dev/ttyUSB0',
    baudRate: 19200,
    retry: RetryPolicies.serial(), // backoff + jitter, tuned for a serial bus
    reconnect: {}, // supervised reconnect + circuit breaker
    });

    With reconnect enabled, operations attempted while the link is down fail with ModbusCircuitOpenError rather than queueing onto a dead bus. It is a member of the ModbusError union, so it can surface from any read() or update() on this service — code that matches exhaustively on _tag should handle it. Defaults are unchanged: with neither option set, operations remain single-shot.

    See the @flux-control/effect-modbus-rs docs for the full policy templates.

    Method Register Description
    operationCommand(deviceId) 0x2501 Start/stop/reverse + fault reset
    frequencyCommand(deviceId) 0x2502 Target output frequency (Hz)
    torqueCommand(deviceId) 0x2503 Torque limit / command (%)
    speedLimitCommand(deviceId) 0x2504 Speed limit (%)
    analogOut1Command(deviceId) 0x2505 Analog output 1 (V)
    analogOut2Command(deviceId) 0x2506 Analog output 2 (V)
    digitalOutCommand(deviceId) 0x2507 Digital output terminals
    Method Register Description
    stateMonitor(deviceId) 0x2520 Operating state flags
    errorDescriptionMonitor(deviceId) 0x2521 Fault code + description
    digitalInStateMonitor(deviceId) 0x2522 Digital input states
    frequencyCommandMonitor(deviceId) 0x2523 Active frequency command
    outputFrequencyMonitor(deviceId) 0x2524 Actual output frequency
    dcBusVoltageCommandMonitor(deviceId) 0x2526 DC bus voltage (V)
    outputCurrentMonitor(deviceId) 0x2527 Output current (A)
    warningDescriptionMonitor(deviceId) 0x2528 Warning code + description
    digitalOutStateMonitor(deviceId) 0x2529 Digital output states
    analogOut1Monitor(deviceId) 0x252A Analog output 1 voltage
    analogOut2Monitor(deviceId) 0x252B Analog output 2 voltage
    analogIn1Monitor(deviceId) 0x252C Analog input 1 (%)
    analogIn2Monitor(deviceId) 0x252D Analog input 2 (%)
    a510CheckMonitor(deviceId) 0x252F Drive series/model ID

    Typed access to all Groups 00–22 via inverter.parameters.group##:

    Group Name Pages
    00 Basic Parameters 4-19 – 4-22
    01 Frequency Parameters 4-37 – 4-38
    02 Accel/Decel Parameters 4-39 – 4-43
    03 Multi-Function Input 4-44 – 4-52
    04 Multi-Function Digital Output 4-53 – 4-59
    05 Multi-Step/Speed 4-60 – 4-66
    06 VFD Protection 4-67 – 4-71
    07 Start/Stop 4-72 – 4-74
    08 Protection 4-75 – 4-79
    09 Communication 4-80
    10 PID Control 4-81 – 4-84
    11 Auxiliary Functions 4-85 – 4-88
    12 Monitoring 4-62 – 4-67
    13 Maintenance 4-68 – 4-71
    14 PLC Setting 4-72
    15 PLC Monitoring 4-73
    16 LCD Function 4-74 – 4-77
    17 Automatic Tuning 4-78 – 4-79
    18 Slip Compensation 4-79
    19 Wobble Frequency 4-79 – 4-80
    20 Speed Control 4-80 – 4-82
    21 Torque & Position Control 4-82 – 4-85
    22 PM Motor 4-85 – 4-88

    Each parameter callable returns { read(), update(value) } for a given deviceId.

    The device-agnostic schema factories now live in the @flux-control/modbus-schema package:

    • makeParam(register, meta) — Simple UInt16 pass-through
    • makeScaledParam(register, factor, meta) — Scaled value (e.g., 0.01 Hz)
    • makeSignedScaledParam(register, factor, meta) — Signed scaled value using two's complement over UInt16 wire
    • makeEnumParam(register, labels, meta) — Labeled selection values
    • makeBitfieldParam(register, flagsClass, bitLayout, meta) — Boolean flags packed into a word
    • makeLookupParam(register, labels, fallback, meta) — Decode-only lookup table with fallback

    Each factory returns a ParamEntry with both Effect-native and synchronous decode/encode APIs. Parameter group files import ParamKind and ParamConfig directly from @flux-control/modbus-schema, and src/parameters/operations.ts hosts the inverter-specific ModbusError-coupled operation types.

    Use SerialTransportService.makeMockTransport with TecoInverterService.mockDevice() — a built-in generator producing a full SlaveDeviceDefinition for the A510 with all registers defaulting to 0.

    import { Console, Effect, Layer } from 'effect';
    import { TecoInverterService } from '@flux-control/effect-teco-westinghouse-inverter';
    import { SerialTransportService } from '@flux-control/effect-modbus-rs';

    const program = Effect.gen(function* () {
    const inverter = yield* TecoInverterService;

    const freq = yield* inverter.frequencyCommand(1).read();
    yield* inverter.frequencyCommand(1).update(50.0);
    const freqAfter = yield* inverter.frequencyCommand(1).read();

    yield* Console.log(`Frequency: ${freq} -> ${freqAfter}`);
    });

    const mockLayer = SerialTransportService.makeMockTransport([TecoInverterService.mockDevice(1)])({
    portPath: '/dev/null',
    baudRate: 9600,
    });

    program.pipe(
    Effect.provide(Layer.provideMerge(TecoInverterService.Default('Rtu'), mockLayer)),
    Effect.scoped,
    Effect.runPromise,
    );

    See examples/readAllRegistersMock.ts for a full walkthrough.

    mockDevice() returns a standard SlaveDeviceDefinition. Override individual register defaults before passing to makeMockTransport:

    const device = TecoInverterService.mockDevice(1);
    const customRegisters = device.holdingRegisters.map((reg) => {
    if (reg.address === 0x2501) return { address: reg.address, default: 5 }; // Running
    if (reg.address === 0x2502) return { address: reg.address, default: 500 }; // 50.0 Hz
    return reg;
    });

    const mockLayer = SerialTransportService.makeMockTransport([
    {
    ...device,
    holdingRegisters: customRegisters,
    },
    ]);
    Property Type Description
    unitId number Modbus slave/unit ID (required)
    coils { address, default }[] Coil registers
    discreteInputs { address, default }[] Discrete input registers
    holdingRegisters { address, default }[] Holding registers (command + monitor + params)
    inputRegisters { address, default }[] Input registers

    Command and monitor registers are TypeScript enums in src/Registers.ts:

    • COMMAND_REGISTERS — 0x2501–0x2507
    • MONITOR_REGISTERS — 0x2520–0x252F
    • GROUP_00_Basic_Parameters through GROUP_22_PM_Motor_Parameters — 0x0000–0x1623
    Action Command
    Install bun install
    Type-check bun run typecheck
    Test bun test
    Run example bun run examples/<name>.ts
    index.tsRe-exports all public API
    src/
    Registers.tsModbus register address enums
    TecoInverterService.tsScoped Effect.Service for A510 communication
    errors.tsError utilities (readOnlyEncodeFailure)
    schemas.tsCommand/monitor wire schemas + formatters
    utils.tsBit helpers (bit)
    parameters/
    index.tsRe-exports all parameter groups
    operations.tsInverter-specific operation types that couple @flux-control/modbus-schema with @flux-control/effect-modbus-rs
    group-00.tsgroup-22.tsParameter configs per group
    examples/
    readOpsRegister.tsRead/write operation command register
    readAllRegisters.tsRead all command + monitor registers
    readAllRegistersMock.tsMock transport walkthrough
    readGroup00Params.tsRead all Group 00 parameters